Yaskawa 120 Series I/O Modules User Manual
Page 297

8 EN Standard Low voltage Directive Compliant I/O Modules
8.1.4 Specifications of the I/O Modules
8-10
4) 100- to 120-VAC or 200- to 240-VAC 8-point Output Modules
Table 8.5 Specifications of 100- to 120-VAC or 200- to 240-VAC 8-point Output Modules
Item
Specifications
Name
100- to 120-VAC or 200- to 240-VAC 8-point Output Module
Model Name
ACOUT-8P
Model No.
JAMSC-120DAO83009 (EN standard)
Rated Voltage
100 to 120 VAC or 200 to 240 VAC
Allowable Voltage Range
80 to 264 VAC
Rated Frequency
50/60 Hz
Allowable Frequency Range
47 to 63 Hz
Maximum Load Current
1.0 A rms/point
Output Voltage Drop
1.0 V rms
Output Delay Times
OFF to ON: 5ms max.
ON to OFF: 1/2 cycle + 5 ms max.
OFF Leakage Current
3 mA max. at 240 VAC, 50 Hz
Minimum Load Current
10 mA rms
Output Type
Triac outputs
Number of Commons
8 (Each output circuit is independent.)
Output Power Supply per Common
Different phase power supplies can be connected to the commons.
External Connections
Removable terminal block with M3 screw terminals.
Output Protection Type
Unprotected outputs (according to IEC 1131-2)
Built-in Fuse
None
Surge Suppressor
Varistor
Other Output Protections
None
Number of Outputs
8
Output Signal Indication
Indicator for each point; lit when the output is ON.
Status saved in internal logic
Status Indication
ACTIVE: Lit during output processing
Insulation Method
Phototriac
Dielectric Strength
1,500 VAC for 1 min. or 1,800 VAC for 1 s between output terminals
and internal circuits and between all output circuits.
Insulation Resistance
100 M
Ω min. at room temperature and humidity between output ter-
minals and ground (measure by a 500-VDC test voltage megohm-
meter)
External Power Supply
100 to 120 VAC or 200 to 240 VAC to drive loads
Derating Conditions
None
Internal Current Consumption
150 mA max. at 5 VDC (with all points ON)
Hot Swapping
(Removal/insertion under power)
Permitted
Maximum Heating Value
9.0W
Approximate Mass
300g
External Dimensions
40.3
×130×103.9 mm (W×H×D)