2 digital output module specifications, 1 100/200-vac 8-point output module – Yaskawa 120 Series I/O Modules User Manual
Page 54
3 Digital I/O Specifications
3.2.1 100/200-VAC 8-point Output Module
3-24
3.2
Digital Output Module Specifications
3.2.1 100/200-VAC 8-point Output Module - - - - - - - - - - - - - - - - - - - - - - - 3-24
3.2.2 100/200-VAC 16-point Output Module - - - - - - - - - - - - - - - - - - - - - - 3-28
3.2.3 12/24-VDC 8-point Output Module - - - - - - - - - - - - - - - - - - - - - - - - 3-32
3.2.4 12/24-VDC 16-point Output Module (Sinking) - - - - - - - - - - - - - - - - 3-36
3.2.5 12/24-VDC 16-point Output Module (Sourcing) - - - - - - - - - - - - - - - 3-40
3.2.6 12/24-VDC 32-point Output Module - - - - - - - - - - - - - - - - - - - - - - - 3-44
3.2.7 12/24-VDC 64-point Output Module - - - - - - - - - - - - - - - - - - - - - - - 3-49
3.2.8 Relay Contact 16-point Output Module - - - - - - - - - - - - - - - - - - - - - 3-55
3.2.1
100/200-VAC 8-point Output Module
1) Performance Specifications
This section describes the performance specifications, circuit configuration, external
connections, and external appearance of the 120-series Digital Output Modules.
Item
Specifications
Name
100/200-VAC 8-point Output Module
Model Name
ACOUT-8P
Model No.
JAMSC-120DAO83000
Rated Voltage
100/200 VAC
Allowable Voltage Range
80 to 264 VAC
Rated Frequency
50/60 Hz
Allowable Frequency Range
47 to 63 Hz
Maximum Load Current
1.0 Arms/point
Output Voltage Drop
1.0 Vrms
Output Delay Times
OFF to ON: 5 ms max.
ON to OFF: 1/2 cycle + 5 ms max.
OFF Leakage Current
3 mA max. at 240 VAC, 50 Hz
Minimum Load Current
10 mArms
Output Type
Triac outputs
Number of Commons
8 (Each output circuit is independent.)
Output Power Supply
per Common
Possible to connect different power supply phases to the commons.
External Connections
Removable terminal block with M3 screw terminals
Output Protection Type
Unprotected outputs (according to JIS B3502)
Built-in Fuse
None
Surge Suppressor
Varistor
Other Output Protection
None
Number of Outputs
8
Output Signal Indication
Indicator for each point; lit when the output is ON.
Status saved in internal logic.
Status Indication
ACTIVE: Lights during input processing.
Insulation Method
Phototriac
Dielectric Strength
1,500 VAC for 1 min or 1,800 VAC for 1 s between output terminals and
internal circuits and between all output circuits.