2 register output specifications, 1 register output modules – Yaskawa 120 Series I/O Modules User Manual
Page 204
5 Register I/O Specifications
5.2.1 Register Output Modules
5-6
5.2
Register Output Specifications
5.2.1 Register Output Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-6
5.2.1
Register Output Modules
1) Performance Specifications
This section describes performance specifications, circuit configuration, external
connections, and appearance of the 120-series Register Output Modules.
Item
Specifications
Name
Register Output Module
Model Name
REGISTER-OUT
Model No.
JAMSC-120RDO34410
Output Circuit
s
Rated Voltage
12/24 VDC
Allowable Voltage Range
10.2 to 30.0 VDC
Output Form
Sinking output
Maximum Load Current
Data output circuit: 100 mA per point, 800 mA per 16 points
Select output circuit: 100 mA per point
Output Voltage Drop
1.5V (0.1A) max.
Output Delay Time
OFF to ON: 1 ms max.
ON to OFF: 1 ms max.
OFF Leakage Current
1 mA max. (24 VDC)
Output Type
Transistor output
Output Protection Type
Data output circuit: Protected output (according to JIS B 3502)
Select output circuit: Unprotected output
(according to JIS B 3502)
Built-in Fuse
One 1-A fuse
(Blowout time: Two minute max. at 200 % of rated current)
Surge suppressor
None
Other Output Protections
None
Number of Outputs
Data output circuit: 16 points
Select output circuit: 16 points
Output Signal Indication
None
External Connections
40-pin connector: one piece
Connector type: FCN-365P040 (made by Fujitsu Ltd.)
Status Indication
R: Lights while the Module is operating normally.
ACTIVE: Lights during output processing
F: Lights when the fuse is blown out or the output power supply
is disconnected.
Insulation Method
Photocoupler
Dielectric Strength
1,500 VAC for 1 min or 1,800 VAC for 1 s between the output
terminals (connected together) and the internal circuits.
Insulation Resistance
100 M
Ω min. at room temperature and humidity between the
output terminals and the ground (measured with a 500 VDC
test voltage megohmmeter).
External Power Supply
12/24 VDC supplied to drive loads
Derating Conditions
None
Internal Current Consumption
400 mA max. at 5 VDC