beautypg.com

Yaskawa 120 Series I/O Modules User Manual

Page 150

background image

4.1 Analog Input Specifications

4-3

4

* Overrange is detected when +10.24 V < Channel input signal or

Channel input signal < -10.24 V

2) Input Characteristics

The following diagram show the input characteristics. Two modes are available:
±2000 mode and 0-4000 mode. The mode is selected by I/O allocation.

Note: (1) For

±2000 mode, if input register value exceeds the range

from -10.24 V to +10.24 V, the analog input value will be
clamped at -2048 or +2048.

(2) For 0-4000 mode, if input register value exceeds the range

from -10.00 V to +10.24 V, the analog input value will be
clamped at 0 or 4048.

Maximum Heating Value

2.3 W

Hot Swapping
(Removal/insertion under power)

Permitted

Approximate Mass

300g

External Dimensions

40.3

×130×103.9 mm (W×H×D)

Recommended Cable

Shielded twisted-pair wires
1.3 mm

2

(AWG16) to 0.5 mm

2

(AWG20)

Item

Specification

Analog input value

Input register value

±2000 mode

0-4000 mode

≤-10.24 V

-2048

0000

-10.00 V

-2000

0000

-5.00 V

-1000

1000

0.00 V

0000

2000

+5.00 V

+1000

3000

+10.00 V

+2000

4000

≥+10.24 V

+2048

4048

Input register value

Analog input value (V)

0-4000 mode

+2000 mode