beautypg.com

Yaskawa 120 Series I/O Modules User Manual

Page 271

background image

6 Installation and Wiring

6.4.3 DC Input Modules

6-44

Input Device

Open collector output (V1

> V2)

Connection

Can be connected.

The voltage resistance of the output transistor in the input
device must be 40 V or more.

Input Device

Output with a diode (V1

> V2)

Connection

Cannot be connected. When the input device is OFF, current indicated by the dot-

ted line in the figure on the left may flow, and the input may
not turn OFF.

Input Device

Output with a resistor and LED (V1

> V2)

Connection

Cannot be connected. When the input device is OFF, current indicated by the dot-

ted line in the figure on the left may flow and apply reverse
voltage to the LED, possibly damaging the LED.

V1: Input signal power supply

V2: Input device power supply

DC Input Module

+Common 1

Photocoupler

Input

Input device

V1

24 VDC

V2

12 VDC

9

V1: Input signal power supply
V2: Input device power supply

DC Input Module

+Common 1

Photocoupler

Input

Input device

V1
24 VDC

V2
12 VDC

9

V1: Input signal power supply
V2: Input device power supply

DC Input Module

+Common 1

Photocoupler

Input

Input device

V1
24 VDC

V2
12 VDC

9