13 Technical Data
SMA Solar Technology AG
80
SSM16-24-IA-IEN105120
Installation Guide
Connecting the Communication
Remote Tripping with Shunt Trip (optional)
Remote Tripping with Undervoltage Release (optional)
Connection Remote Tripping (optional)
Feedback Contact with Remote Tripping (optional)
Type of terminal
Spring terminal
Maximum connection cross section
0.08 mm
2
… 2.5 mm
2
Cable entry via cable gland
M25
Cable gland clamping zone
7 mm … 14 mm
Recommended cable type
4 mm x 2 mm x 0.5 mm Li2YCYv (TP)
Number of the provided contactable shield
clamps
*
*
maximum shield diameter: 8 mm
2
Nominal voltage
220 V
AC
… 240 V
AC
Extended operating range
–30% … +10%
Nominal frequency
50 Hz / 60 Hz
Power consumption
100 VA
Nominal voltage
220 V
AC
… 240 V
AC
Extended operating range
− 15% … +10%
Nominal frequency
50 Hz / 60 Hz
Power consumption
3 VA
Type of terminal
Spring terminal
Maximum connection cross section
0.5 mm
2
… 6 mm
2
Cable entry via cable gland
M25
Cable gland clamping zone
7 mm … 14 mm
Nominal voltage
250 V
AC/DC
Nominal current
5 A
AC
/ 0.15 A
DC
Format
Inverter