13  Technical Data

SMA Solar Technology AG

80

SSM16-24-IA-IEN105120

Installation Guide

Connecting the Communication

Remote Tripping with Shunt Trip (optional)

Remote Tripping with Undervoltage Release (optional)

Connection Remote Tripping (optional)

Feedback Contact with Remote Tripping (optional)

Type of terminal

Spring terminal

Maximum connection cross section

0.08 mm

2

… 2.5 mm

2

Cable entry via cable gland

M25

Cable gland clamping zone

7 mm … 14 mm

Recommended cable type

4 mm x 2 mm x 0.5 mm Li2YCYv (TP)

Number of the provided contactable shield
clamps

*

*

maximum shield diameter: 8 mm

2

Nominal voltage

220 V

AC

… 240 V

AC

Extended operating range

–30% … +10%

Nominal frequency

50 Hz / 60 Hz

Power consumption

100 VA

Nominal voltage

220 V

AC

… 240 V

AC

Extended operating range

− 15% … +10%

Nominal frequency

50 Hz / 60 Hz

Power consumption

3 VA

Type of terminal

Spring terminal

Maximum connection cross section

0.5 mm

2

… 6 mm

2

Cable entry via cable gland

M25

Cable gland clamping zone

7 mm … 14 mm

Nominal voltage

250 V

AC/DC

Nominal current

5 A

AC

/ 0.15 A

DC

Format

Inverter