8 Disconnecting the Sunny String-Monitor
Installation Guide
SSM16-24-IA-IEN105120
47
8 Disconnecting the Sunny String-Monitor
1. If there is a DC circuit breaker on the Sunny String-Monitor, disconnect it. This ensures that there
is no current flowing through the Sunny-String-Monitor.
2. If there is no DC circuit breaker, disconnect the Sunny Central (see the installation guide for the
Sunny Central).
3. If there are fuses in the Sunny Central, remove them. Use an LV/HRC fuse handle to do this.
4. If there are no fuses in the Sunny Central, remove the fuses in the DC main distributor.
6. Disconnect all the DC plug connectors.
%"/(&3
Risk of lethal electric shock.
• Pay attention to the safety rules.
– Disconnecting the device
– Ensure that the device cannot be reconnected
– Ensure that no voltage or current is present
– Cover or isolate adjacent live elements
%"/(&3
Risk of lethal electric shock. The discharge time of the capacitors is longer than 5 minutes.
• After disconnection, wait until the capacitors have discharged.
8"3/*/(
Danger of burns from touching hot component parts.
• Wear gloves when working on the device.
5.
%"/(&3
Risk of lethal electric shock.
• Only open the isolation terminals in a no-load condition.