Input Data at 40 °C Ambient Temperature
PV array configuration
Negative or positive grounded, isolated
Maximum permissible DC voltage
U
DC
1 000 V
Maximum permissible DC current
I
DC
320 A
Number of measuring inputs
24
Maximum number of connections per
measuring input
*
*
optional
2
Possible string fuses
10 A / 12 A / 16 A / 20 A
Maximum string current per measuring
input for 10 A string fuse
7 A
Maximum string current per measuring
input for 12 A string fuse
**
**
reduction factor 0.7
8.4 A
Maximum string current per measuring
input for 16 A string fuse
11.2 A
Maximum string current per measuring
input for 20 A string fuse
***
***
reduction factor 0.665
13.3 A
measuring voltage supply
35 V
DC
… 55 V
DC