beautypg.com

12 troubleshooting, 1 led signals, Troubleshooting – SMA SSM16-11 User Manual

Page 68: Led signals

background image

12  Troubleshooting

SMA Solar Technology AG

68

SSM16-24-IA-IEN105120

Installation Guide

12 Troubleshooting

12.1 LED signals

Symptom

Cause

Corrective measures

LED not lighting up.

Problems with the power supply

• Check the +55 V power

supply at the connection area
of the Sunny String-Monitor in
question.

LED 1 does not glow.

Theft protection is activated.

• Check the wiring of the theft

protection.

LED 2 does not glow.

Surge arrester has tripped.

• Replace a defective

protection module in the surge
arrester.

LED 3 does not light up for
more than 5 minutes.

Problems with the data cable

• Check data cable between

Sunny Central and Sunny
String-Monitor, and between
the individual Sunny
String-Monitors.

LED 4 glows red.

Failure of the control board of
the string current monitoring

• Contact the SMA Serviceline.

This manual is related to the following products: