Assemble the sunclix dc plug connectors – SMA SSM16-11 User Manual
Page 32
6 Electrical Connection
SMA Solar Technology AG
32
SSM16-24-IA-IEN105120
Installation Guide
Procedure:
• Assemble the SUNCLIX DC plug connectors
• Connect the SUNCLIX DC plug connectors to the Sunny String-Monitor
Assemble the SUNCLIX DC plug connectors
Figure 13: SUNCLIX DC plug connector
Use the following procedure to assemble each DC plug connector.
1. Cut the wire to length and strip 12 mm off the insulation.
2. Guide the stripped wire all the way into the DC
plug connector. Ensure the correctness of the
polarity assignment and of the type of plug.
3. Push the clamping clip downward.
☑ The clamping clip snaps audibly into place.
☑ The stranded wire can be seen inside the
clamping clip chamber.
Position
Designation
A
Negative DC plug connector
B
Positive DC plug connector
+
++
++