3. Adapt the identification process for each String Monitor Unit.
• Select the String Monitor Unit you want.
• In the "Parameters" area, select SSM Identifier.
• In the "Channel Value" area, enter a unique identification number between 1 and 40.
• Select [Set]. This saves the setting.
10.3 Setting Parameters for String Current Monitoring
10.3.1 Overview of the Program Window
Figure 21: Buttons and input windows for parameterization of the Sunny String-Monitor
Position
Designation
A
Second-tier designation of the device in the plant tree
B
Labeling of the String Monitor Unit with the serial number of the Piggy-Back
for data processing in the plant tree
C
"Parameters" tab
D
"Parameters" area
E
"Channel value" area
F
[Set] button