6  Electrical Connection

SMA Solar Technology AG

34

SSM16-24-IA-IEN105120

Installation Guide

5. Insert the DC plug connectors with sealing plugs into the remaining DC inputs on the Sunny

String-Monitor. This way you seal the Sunny String-Monitor.

6.2.4 Connecting the PV Strings to Tyco, MC3, and MC4 Plug

Connectors

1. Remove the sealing plugs from the plugs.
2. Connect the DC plug connectors.

6.3 Connecting the DC Main Cable

Requirement:

☐ The correct terminal cross section for the main DC cable has been chosen.

Terminal Cross Section for Copper Cable

/05*$&

Damage to the electronics due to wrong cable installation.
In order for the Sunny String-Monitor and Sunny Central to work properly, EMC guidelines must be
observed.

• Lay the DC main cable and the data cable separately and at a distance greater than 400 mm

from one another.

Connection

terminal

Number of

cables

Terminal cross section

Round,

single-strand

Round,

multi-strand

Sectoral,

single-strand

Sectoral,

multi-strand

maximum

240 mm

2

1

*

*

Sunny String-Monitor SSM16/24-11 with bottom plate: connection of 1 cable per DC terminal possible.

25 mm

2

50 mm

2

25 mm

2

240 mm

2

50 mm

2

185 mm

2

35 mm

2

240 mm

2

2

**

**

Sunny String‑Monitor SSM16/24-11 without bottom plate: connection of 2 cables per DC terminal possible.

25 mm

2

50 mm

2

25 mm

2

120 mm

2

50 mm

2

120 mm

2

35 mm

2

120 mm

2

maximum

300 mm

2

1

*

-

150 mm

2

300 mm

2

150 mm

2

185 mm

2

150 mm

2

240 mm

2

2

**

70 mm

2

70 mm

2

185 mm

2

95 mm

2

185 mm

2

95 mm

2

185 mm

2