2  Safety

Installation Guide

SSM16-24-IA-IEN105120

11

Electric Shock

The Sunny String-Monitor is connected to high voltages. Work on the Sunny String-Monitor is only
allowed if the power is disconnected and in compliance with the guidelines that apply at the
installation location.

• Disconnecting the device:

– Remove the DC fuses in the central inverter or main DC distributor, such as the Sunny Main

Box, in a no-load condition.

– Switch off the DC circuit breaker in the Sunny String-Monitor.
– Only open or close the isolation terminals in the Sunny String-Monitor in a no-load condition.
– Only insert or remove the fuses when wearing personal protective gear.
– Only plug in or unplug the Solar Plug when no load is present.

• Ensure that the device cannot be reconnected.
• Ensure that no voltage is present in the system.
• Ground and short-circuit.
• Cover or safeguard any adjacent live components. Protective covers must always be fitted.

If there is a grounding fault, grounded plant sections may be presumed live.

• Ensure there is no voltage present before touching.

Operating a damaged Sunny String-Monitor may cause severe injury from electric shock.

• The Sunny String-Monitor may only be used when it is technically faultless and safe to operate.
• Operate the Sunny String-Monitor only without visible damage and check regularly for visible

damage.

• Ensure that all external safety equipment is freely accessible at all times and is regularly checked

for proper functioning.

Burns

Some components, such as fuses, can become hot during operation.

• Wear safety gloves when working on the device.