With the Sunny Central inverters in the CP and the HE-20 series, you can set the parameters on the
PC via the WebBox interface and read the mean values and the messages.
With the parameterization, the Sunny String-Monitor can determine the total malfunction of a string
within a polling interval. Slightly elevated string currents are reliably detected in several polling
intervals and distinguished from typical current fluctuations of the PV array.
The following describes:

• The circumstances under which the string current is monitored
• The intervals at which data is transmitted
• Which parameters are important for the sensitivity with which the string current is monitored.

Requirements for Activating the String Current Monitoring

☐ The DC power of the PV array exceeds 5% of the nominal AC power of the Sunny Central.

P

DC

> 0.05 * P

AC nom

☐ The string current mean value of the individual groups is equal or greater than 0.5 A.

I

M String

≥ 0.5 A

Error Sum

The error sum is a measure of the sensitivity of the string current monitoring. It can be parameterized
via the tripping time and tolerance, and is described by the following formula:

The individual error sums of the measuring channels are reset at 00:00 o'clock.

Value

Designation

P

DC

PV array power

P

AC nom

Sunny Central nominal AC power

Value

Designation

I

M String

Mean value of string-current from each group