13  Technical Data

Installation Guide

SSM16-24-IA-IEN105120

73

DC Main Connection

DC String Connection to MC4 Plug Connector

DC String Connection to MC3 Plug Connector

DC String Connection to Plug Connector SUNCLIX

DC String Connection to Disconnection and Measurement Terminal

Type of terminal

Cage clamp

Maximum connection cross section

240 mm

2

/ 300 mm

2

Suitable connector material

Copper/aluminum

Number of connection terminals per
DC output

*

*

Sunny String-Monitor SSM16-11 with bottom plate: connection of 1 cable per DC terminal possible.

Sunny String‑Monitor SSM16-11 without bottom plate: connection of 2 cables per DC terminal possible.

1 / 2

Cable entry via cable gland

M40

Cable gland clamping zone

13 mm … 32 mm

Cable cross section

6 mm

2

Maximum rated current

30 A

Cable cross section

4 mm

2

Maximum rated current

20 A

Cable type

PV1-F

Cable cross section

2.5 mm

2

… 6 mm

2

Cable diameter

5 mm … 8 mm

Maximum rated current

40 A

Type of terminal

Spring terminal

Maximum connection cross section

0.2 mm

2

… 6 mm

2

Cable entry via multiple cable gland

M50

Grip range of multiple cable gland

5.0 mm … 5.5 mm / 5.6 mm … 6.0 mm /
6.1 mm … 7.0 mm / 7.1 mm … 8.0 mm /

8.1 mm … 9.0 mm