Page 58: Recommissioning at a restart

Commissioning
Operating Manual PMCprotego S22(C)
1002529EN02
58
The inputs and outputs on the safety card can be tested using
}
The dynamic program display in the safety card's Configurator
}
PDrive and PScope from PMCmotion control tools
7.3
Recommissioning
7.3.1
Recommissioning at a restart
The timing diagram below illustrates the signal sequence of the servo amplifier and safety
card at a restart. The safety card has already been configured (see "Initial commissioning")
Servo Amplifier
24 V
X4/1
BTB/RTO
X3B/14,15
L1, L2, L3
X0
X8
Safety Card Sx
24 V
X30/1
Reset
X30/20
Ready
X30/16
STO Acknowledge
X30/5
SS1 Activate
X30/1
Servo Amplifier
STO-ENABLE
HW-/SW-Enable
Enable U, V, W
Motor n
t1 = 15 ms
t2 = 500 ms
t3 = 10 s
t4 > 100 ms
U
0
U
0
U
0
U
0
U
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
This manual is related to the following products:
- PMCprimo DriveP.24/ABB/4/0/0/208-480VAC PMCprimo DriveP.06/AB0/2/0/0/208-480VAC PMCprimo DriveP.06/AB0/3/0/0/208-480VAC PMCprimo DriveP.24/AA0/5/0/0/208-480VAC PMCprotego D.06/000/0/0/2/208-480VAC PMCprotego D.24/000/0/0/2/208-480VAC PMCprotego D.06/010/0/0/2/208-480VAC PMCprotego D.06/100/0/0/2/208-480VAC PMCprotego D.06/200/0/0/2/208-480VAC PMCprotego D.24/200/0/0/2/208-480VAC PMCprotego D.24/100/0/0/2/208-480VAC PMCprotego D.24/010/0/0/2/208-480VAC PMCprotego S2-2 PMCprotego S2-2-C