Function description
Operating Manual PMCprotego S22(C)
1002529EN02
22
}
Braking ramp in normal operation
The drive starts with the configured braking ramp when safety function SS1 has been
activated. Once the time has elapsed, STO is activated.
}
ESTOP braking ramp:
The drive starts with the configured braking ramp when
–
there is an internal error
–
limit values are exceeded
}
Safety function STO is activated when
–
the actual braking period is longer than the configured STO delay time.
–
the configured limit value for the position error is exceeded.
–
another error occurs while SS1 is activated
–
the STO delay time has elapsed
}
Automatic STO at standstill
A standstill threshold for activating the safety function STO can be specified in the Con
figurator.
Safety function STO is activated when
–
standstill is achieved while the STO delay time is running.
–
the STO delay time has elapsed.
Input and output assignment
}
Input
–
X30/1: SS1 Activate
}
Outputs
–
X30/5: STO Acknowledge
–
X30/16: Ready
Prerequisites for normal operation:
}
Input "SS1 Activate" and "Reset": "1" Signal (+24 VDC)
}
"Ready" output: "1" Signal (+24 VDC). The safety card is ready for operation.
}
"STO Acknowledge" output: “0” Signal
The safety function is activated via
}
1/0 pulse edge at the input "SS1 Activate"
or
}
1/0 pulse edge at the "Reset" input
}
Internal error
Signal status of the inputs "SS1 Activate" and "Reset"
}
The STO delay time starts when one of the two inputs "SS1 Activate" or "Reset" is set
to "0". The safety function "STO" is activated once the STO delay time has elapsed.
}
The safety function "STO" is activated immediately if the second input is also set to "0".
}
The safety function "STO" is always activated when both the inputs "SS1 Activate" and
"Reset" are set to "0".
- PMCprimo DriveP.24/ABB/4/0/0/208-480VAC PMCprimo DriveP.06/AB0/2/0/0/208-480VAC PMCprimo DriveP.06/AB0/3/0/0/208-480VAC PMCprimo DriveP.24/AA0/5/0/0/208-480VAC PMCprotego D.06/000/0/0/2/208-480VAC PMCprotego D.24/000/0/0/2/208-480VAC PMCprotego D.06/010/0/0/2/208-480VAC PMCprotego D.06/100/0/0/2/208-480VAC PMCprotego D.06/200/0/0/2/208-480VAC PMCprotego D.24/200/0/0/2/208-480VAC PMCprotego D.24/100/0/0/2/208-480VAC PMCprotego D.24/010/0/0/2/208-480VAC PMCprotego S2-2 PMCprotego S2-2-C