beautypg.com

LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual

Page 94

background image

LAARS Heating Systems

Page 90

Label

Description

How to Reach

Lead lag off

hysteresis

When the Lead/Lag function is enabled, the

control system will not shut off the boilers until

the temperature at the System sensor rises to the

Lead/Lag CH setpoint plus a hysteresis value

(normally about 10°F).

Home screen/ View Lead/Lag button/

Lead/Lag screen/ Lead/Lag Master

button/ Lead/Lag Master screen/

Configure button/ Lead/Lag Master

Configuration screen/ Advanced Settings

button/ Left- or Right- arrow buttons/

Modulation screen.

Lead lag on

hysteresis

When the Lead/Lag function is enabled, the

control system will not fire the boilers until the

temperature at the System sensor drops to the

Lead/Lag CH setpoint minus a hysteresis value

(normally about 10°F).

If Lead/Lag enabled –

Home screen/ View Lead/Lag button/

Lead/Lag screen/ Lead/Lag Master

button/ Lead/Lag Master screen/

Configure button/ Lead/Lag Master

Configuration screen

Lead lag P

gain

This is part of the damping function

(“Proportional”) used when the controller

interprets the input from the System sensor.

Home screen/ View Lead/Lag button/

Lead/Lag screen/ Lead/Lag Master

button/ Lead/Lag Master screen/

Configure button/ Lead/Lag Master

Configuration screen/ Advanced Settings

button/ Left- or Right- arrow buttons/

Modulation screen

Lead/Lag

Slave Enable

Select Enable Slave for Built-in Lead/Lag

Master. Be sure this is turned on for each

controller in the system.

Home screen/ Select controller/ Status

Summary screen/ Configuration button/

Configuration screen/ Select line for LL

Slave Configuration/ Lead/Lag Slave

Configuration screen

Lead/

Lag Slave

Sequence

Order

Enter the position of this Slave in the sequence.

Be sure to enter this for each Slave in the

system.

Home screen/ Select controller/ Status

Summary screen/ Configuration button/

Configuration screen/ Select line for LL

Slave Configuration/ Lead/Lag Slave

Configuration screen

Lead/

Lag Slave

Modbus

Address

Each slave must have a unique Modbus address.

Be sure to enter this for each controller in the

system.

Home screen/ Select controller/ Status

Summary screen/ Configuration button/

Configuration screen/ Select line for LL

Slave Configuration/ Lead/Lag Slave

Configuration screen

Lead/Lag

Outdoor

Reset Enable

Enable = Outdoor Reset feature turned on

Home screen/ View Lead/Lag button/

Lead/Lag screen/ Lead/Lag Master

button/ Lead/Lag Master screen/

Configure button/ Lead/Lag Master

Configuration screen/ Advanced Settings

button/ Left- or Right- arrow buttons/

Outdoor Reset screen

Lead/Lag

Outdoor

Reset

low water

temperature

This parameter is used as the normal setpoint

above the point where Outdoor Reset stops

adjusting for a higher outdoor temperature (the

Max. Outdoor Temperature value)

Home screen/ View Lead/Lag button/

Lead/Lag screen/ Lead/Lag Master

button/ Lead/Lag Master screen/

Configure button/ Lead/Lag Master

Configuration screen/ Advanced Settings

button/ Left- or Right- arrow buttons/

Outdoor Reset screen

This manual is related to the following products: