beautypg.com

3 venting and combustion air, 1 combustion air – LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual

Page 11

background image

NeoTherm Boilers and Water Heaters

Page 7

shall be of the same cross-sectional area as the free

area of the openings to which they connect.
Method 1

: Two permanent openings, one

commencing within 12” (300 mm) of the top and

one commencing within 12” (300 mm) of the

bottom, of the enclosure shall be provided. The

openings shall communicate directly, or by ducts,

with the outdoors or spaces that freely communicate

with the outdoors. When directly communicating

with the outdoors, or when communicating to the

outdoors through vertical ducts, each opening shall

have a minimum free area of 1 square inch per

4000 Btu/hr (550 square mm/kW) of total input

rating of all equipment in the enclosure. When

communicating to the outdoors through horizontal

ducts, each opening shall have a minimum free

area of not less than 1 square inch per 2000 Btu/

hr (1100 square mm/kW) of total input rating of all

equipment in the enclosure.

Section 3

VentInG anD ComBUStIon aIr

3.1

Combustion air

NeoTherm boilers and water heaters must have

provisions for combustion and ventilation air in

accordance with the applicable requirements for

Combustion Air Supply and Ventilation in the

National Fuel Gas Code, ANSI Z223 1; or in Canada,

the Natural Gas and Propane Installation Code, CSA

B149.1. All applicable provisions of local building

codes must also be adhered to.
A NeoTherm unit can take combustion air
from the space in which it is installed, or the
combustion air can be ducted directly to the unit.
Ventilation air must be provided in either case.

3.1.1

Combustion air from room

In the United States, the most common requirements

specify that the space shall communicate with the

outdoors in accordance with Method 1 or 2. (See the

following descriptions.) Where ducts are used, they

table 3a - Horizontal terminations for Indoor Use

PVC

CPVC

Stainless Steel

Polypropylene

Ducted Air

Exhaust

Ducted Air

Exhaust

Ducted Air

Exhaust

Ducted Air

Exhaust

CA008100

CA008300

CA008100

CA008300

CA008200

D2004500

CA008500

CS008500

PVC

CPVC

Stainless Steel

Polypropylene

Ducted Air

Exhaust

Ducted Air

Exhaust

Ducted Air

Exhaust

Ducted Air

Exhaust

CA008400

CA008300

CA008400

CA008300

CA008500

CA008500

CA008500

CA008500

table 3b - Vertical terminations for Indoor Use

table 3c - outdoor terminations

Ducted Air

Exhaust

CA008700

CA008900

table 4 - required Combustion air Pipe material

Material

United States

Canada

ABS

ANSI/ASTM D1527

The air pipe material must be chosen based upon

the intended application of the boiler, and must

be installed according to the vent manufacturer’s

installation instructions.

PVC, sch. 40

ANSI/ASTM D1785 or D2665

CPVC, sch. 40

ANSI/ASTM F441

Single wall galv. steel

26 gauge

Polypropylene

ULC-S636 Class 2C

This manual is related to the following products: