beautypg.com

LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual

Page 85

background image

NeoTherm Boilers and Water Heaters

Page 81

9.5

Setup for Domestic Hot Water on

a lead/lag System

There are three ways that a NeoTherm 1000 system

can be set up to provide domestic hot water. Two

of them involve the use of an indirect water heater.

In a system including an indirect water heater, hot

water is circulated through a piping loop which runs

through an insulated water tank. Heat from the water

in the loop is transferred to the water in the tank, and

the heated water in the tank is used as domestic hot

water.

Setup type 1 –
All of the boilers in the system can be set up to react

together if there is a call for domestic hot water. This

arrangement can be used for NTH or NTV units.

When NTH units are used in this kind of setup, the

demand for domestic hot water (DHW) is given

priority over the demand for central heat (CH). If

the system is producing heat for a CH demand, and

a call for DHW arrives, all of the boilers will stop

producing heat for CH, and the whole system will

respond to the DHW demand. The DHW pump will

start circulating water through the loop in the indirect

water heater. The System sensor is used to control

modulation in this configuration, so sensor placement

is critical.
This arrangement can be cumbersome if the demand

for domestic hot water is a lot less than the demand

for central heating. This can result in multiple boilers

“idling” as they wait for the DHW demand to be

satisfied.

Caution

For NTH units - This arrangement can only be

used in applications where all of the components

in the system are rated for both the maximum

hydronic temperature and the maximum DHW outlet

temperature.
The setup for this is all done from within the Lead/

Lag system. You will need to set up an LL CH

setpoint and a separate LL DHW setpoint, and assign

the priority to the DHW demand.

The input from the aquastat is brought to terminals

5 and 6 on TB6 on the controller which is acting as

the Lead/Lag Master. (Usually, this is the Primary

controller on Boiler 1.)

1. From the Home screen (Fig. 111), press the

View Lead Lag button.

fig. 111 – Home Screen


2. If the system was running, the following screen

would normally show the current activity of

each unit in the multiple boiler arrangement.

See Fig. 112.

fig. 112 – lead/lag Screen

3. Press the button for Lead Lag Master. Fig. 113

shows the screen that follows.

This manual is related to the following products: