3 checking lead/lag operating information – LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual
Page 40
LAARS Heating Systems
Page 36
fig. 26 - numeric entry Screen
Anyone can view all of the parameters. However,
to change most of the parameters, you will need a
password.
In the center of the screen shown in Fig. 27, the
system is telling you that it wants you to log in.
fig. 27 - login required
The screen used to Login is similar to the Keyboard
screen shown in Fig. 25.
8.3
While operating - Checking
lead/lag operating Information
The Lead/Lag function controls the operation of all
of the boilers connected to the system, and some
system components. For a complete explanation of
Lead/Lag, see the beginning of Section 9.
In this section, we will explain how to check the
Lead/Lag information while the system is running.
1. From the Home screen (Fig. 28), press the
View Lead Lag button.
fig. 28 - Home Screen
Up to 8 controllers, or up to 4 boilers, can be
displayed on the Home page. The icon for
each system will appear in one of four colors:
Blue
Normal operation
Red
Lockout
Gray
Standby mode
(Burner switch off)
Gray and
crossed out
Communication
problem
Yellow
Hold state. This
could be Anti short
cycle, fan speed
transitions, etc.