LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual
Page 117
NeoTherm Boilers and Water Heaters
Page 113
Code Description
L or
H
Procedure
196
Invalid ignition source setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
197
Invalid interlock open response setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
198
Invalid interlock start check setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
199
Invalid LCI (Limit Control Input) enable
setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
200
Invalid lightoff rate setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
201
Invalid lightoff rate proving setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
202
Invalid MFEP (Main Flame Establishing
Period) time setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
203
Invalid MFEP (Main Flame Establishing
Period) flame failure response setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
204
Invalid NTC sensor type setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
205
Invalid Outlet high limit response
setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
207
Invalid PII (Pre-Ignition Interlock)
enable setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.