beautypg.com

Job e – set up the modbus control addressing – LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual

Page 64

background image

LAARS Heating Systems

Page 60

5. At this point, you have disabled the Master

function on one of the controllers. You will

need to repeat the process for each of the other

controllers in the system (except the Primary

Controller on Boiler 1).

Go to the Operator Interface on the next boiler.

Repeat steps 1 through 4 for the first controller

on that boiler.

6. Repeat the steps listed above for each of the

other controllers on the system. Disable the

Master function on each of them.

Job e – Set Up the modbus Control

addressing

(This is an individual function – do this for each of the controls
Use the separate Operator Interface on each boiler.)

Do this on any system with multiple boilers.

note – Do not connect the Modbus wiring yet. The

controls must be set up and addressed correctly

before the wiring is complete. If the wiring is attached

before the control Modbus addresses are changed,

there will be multiple controls with the same address,

and the system will not work.

1. When the system is operating under the control

of the Lead/Lag system, the Lead/Lag Master

needs a way to identify each controller in each

of the boilers. On a system with four boilers

there will be eight separate controllers. You

will need to give each of these controllers a

unique Modbus address. (Notice that this is

different from the name of the controller. We

set the controller names in a previous step.)

2. Power up all of the boilers in the system. It

will take a minute for each Operator Interface

to “synchronize” with its two controllers.

3. Start at the Home screen on the first boiler. See

Fig. 65.

fig. 65 – Home Screen

4. Press the Setup button in the lower right-hand

corner to go to the Display Setup screen.

fig. 66 – Display Setup Screen

5. Press the Modbus System Configuration

button. Figure 67 shows the Modbus System

Configuration screen.

Fig. 67 – Modbus System Configuration Screen

6. The first number on each line (01, 02, etc.) is

the Modbus control address. Let’s set up the

Modbus address for the first controller in the

line - the Primary controller on Boiler 1. Press

the top line – Boiler 1 Primary.

7. Press the Change Address button. You need to

know the installer-level password to change

the address, so the system will ask you to log

in. (For more information on the passwords

and logging in, see the section on “Using the

Touchscreen.”) Type in the installer-level

password and press the OK button.

This manual is related to the following products: