Code Description

L or

H

Procedure

26

Internal fault:
Static flame ripple

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

27

Internal fault:
Flame rod shorted to ground detected

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

28

Internal fault:
A/D linearity test fails

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

29

Internal fault:
Flame bias cannot be set in range

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

30

Internal fault:
Flame bias shorted to adjacent pin

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

31

Internal fault:
SLO electronics unknown error

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

32-

46

Internal fault:
Safety Key 0 through 14

L

Internal fault
1. Reset module
2. If fault repeats, replace module.

47

Flame Rod to ground leakage

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

48

Static flame (not flickering)

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

49

24 VAC voltage low/high

H

1. Check the module and display connections.
2. Check the module power supply and make

sure that frequency, voltage and VA meet the

specifications.

50

Modulation fault

H

Internal sub-system fault.
1. Review alert messages for possible trends.
2. Correct possible problems.

51

Pump fault

H

Internal sub-system fault.
1. Review alert messages for possible trends.
2. Correct possible problems.

52

Motor tachometer fault

H

Internal sub-system fault.
1. Review alert messages for possible trends.
2. Correct possible problems.