beautypg.com

3 troubleshooting table – LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual

Page 106

background image

LAARS Heating Systems

Page 102

12.3 troubleshooting table

This table includes a listing of the faults that might be generated by the controllers, and displayed on the

Operator Interface. Some of these can be corrected by an installer changing a parameter, while other

conditions are more complicated, and will require a service technician.
The first column lists the code number that will appear at the beginning of the Lockout or Hold message in

the orange bar at the bottom of the screen. The second column lists the text as it will appear on the Operator

Interface. The third column shows whether the condition will cause a Hold, or Lockout, or both. The fourth

column lists some suggestions for corrective action.

Code Description

L or

H

Procedure

1

Unconfigured safety data

L

1. New device, complete device configuration and

safety verification.
2. If fault repeats, replace module

2.

Waiting for safety
data verification

L

1. Device in Configuration mode and safety

parameters need verification and a device
needs reset to complete verification.
2. Configuration ended without verification, re

enter configuration, verify safety
parameters and reset device to complete

verification.
3. If fault repeats, replace module.

3

Internal fault:
Hardware fault

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

4

Internal fault:
Safety Relay key feedback error

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

5

Internal fault:
Unstable power (DC DC) output

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

6

Internal fault:
Invalid processor clock

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

7

Internal fault:
Safety relay drive error

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

8

Internal fault:
Zero crossing not detected

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

9

Internal fault:
Flame bias out of range

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

10

Internal fault:
Invalid burner control state

L

Internal fault
1. Reset module
2. If fault repeats, replace module.

This manual is related to the following products: