Code Description
L or
H
Procedure
159
Main valve OFF
L
1. Check Main Valve terminal wiring and correct
any errors.
2. Reset and sequence the module. If fault
persists, replace the module.
160
Ignition ON
L
1. Check Ignition terminal wiring and correct any
errors.
2. Reset and sequence the module. If fault
persists, replace the module.
161
Ignition OFF
L
1. Check Ignition terminal wiring and correct any
errors.
2. Reset and sequence the module. If fault
persists, replace the module.
164
Block intake ON
L
1. Check wiring and correct any errors.
2. Inspect the Block Intake Switch to make sure it
is working correctly.
3. Reset and sequence the module.
4. During Standby and Purge, measure the
voltage across the switch. Supply voltage should
be present. If not, the Block Intake Switch is
defective and needs replacing.
5. If the fault persists, replace the relay module.
165
Block intake OFF
L
1. Check wiring and correct any errors.
2. Inspect the Block Intake Switch to make sure it
is working correctly.
3. Reset and sequence the module.
4. During Standby and Purge, measure the
voltage across the switch. Supply voltage should
be present. If not, the Block Intake Switch is
defective and needs replacing.
5. If the fault persists, replace the relay module.
172
Main relay feedback incorrect
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
174
Safety relay feedback incorrect
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
175
Safety relay open
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
176
Main relay ON at safe start check
L
Internal Fault.
1. Reset Module.
2. If fault repeats, replace module.