Undefined output, Query condition, Output type – Interlogix Monitor XL Advanced Installation Guide User Manual
Page 41
21-3602E rev1.5
Monitor xL™ Advanced Installation Guide
35
Undefined Output
LCD Screen
An Undefined Output is
turned off. It can be
changed to any “Query
? 0000.00 Undef
Save
?
Bxxx:0
Condition” by changing the first 0 to the letter of any
programming section i.e. “S” for System, “A” for Area
etc. (see page 1 for a full list).
Pressing the keypad button below “
? “ when the output number
is associated with a module will display the module’s number (i.e.
module # XX), what type it is (e.g. Input/Output module), the
module’s serial number and its output number range.
Query Condition
“q” will represent the first
letter of a programming
section.
? qnnn.cc Query
Save
?
Bxxx:0
“nnn” is the number in the programming section
range that the output is assigned to. E.g. 001 – 016
for Areas, 001 – 050 for Schedules. However,
“System” is 000 – 000 because there are no specific
numbers of anything contained in it. ‘000’ would be
entered for “System”.
“cc” is the condition code number for the Query
from the Output Selections tables.
A Query can always be changed from one type to
another and can be set as undefined. E.g. a system
siren (S000.07) can be changed to Area 5 is OFF
(A005:14).
Output type
In the next keypad screen
after pressing Save, any
basic output assignment
T itt Timer
Save
?
Bxxx:1
can be timed or just follow what the output is
supposed to do.
“i” represents entering a “0” for the output to be a
non-inverted output (e.g. output turns positive) or “1”
for an inverted output (e.g. output turns negative).
“tt” mainly assigns a time delay to the output
from the Timer Delay Codes Table, page 37. If
“00” is entered here it follows a “normal” output
action e.g. “When the system is in alarm”. The
timer delay table begins with entering from 01
being a 1 second timer to 31 being a 1-week
timer. Special entries here are “98” which will
make the output a toggle type. Meaning e.g.
associated keypad command keys when
pressed will turn the output on and the same key
sequence pressed again will turn it off. Entering
“99” is an additional way to turn the output off so
it will never activate.
These previous screens are the only ones that will
permit programming simple outputs using the
following Output Selections tables. The next
output programming screens will only appear
when an advanced output has been programmed
using the Director Software and sent to the panel
with a communications method e.g. direct
connection, IP module. After an advanced
equation output has been sent to the panel,
viewing the related output in the “B” output’s
programming section on an LCD keypad will
display additional screens for it like the following:
A Logic equation output
where “ff” is a following
condition code.
L ff Logic
Save
?
Bxxx:2
A logic equation that is
very complicated and can
only be viewed in the
Complex-Director
Save
?
Bxxx:0
Director
software
program.
An output in the outputs
section has been e.g.
improperly programmed.
Error! Bxxx,eee
Save Bxxx:2
This condition will only display in the output’s “B”
programming section on an LCD keypad and not
in Status.
Warning: Ordinarily, this type of error will
display as a result of a complicated equation
output done in the Director software and sent to
the panel. This will make it necessary to correct
the error in the Director software and re-send
the information to the panel.
“xxx”
is the output number, 001 – 128, where
the error first occurred. It may not be the same
as the output you are currently viewing. All
outputs after the one affected will display “Error”
and not display any of their settings on the LCD
screen. Outputs after the one in fault will also
cease to operate. All outputs before the one
affected will display their settings and operate
normally.
“eee”
will tell you the type of error. Refer to the
following error list.
Error
Code
Description Possible
Solution
000 Not
applicable.
Notify dealer if
persistent.
001 Program
section
unknown.
Check program
section letter i.e.
“A” for Area, “M”
for module etc.
002 Logic
equation
condition is
unknown.
Panel firmware
version may be
incompatible with
Director ver.
003 Program
section range
number
invalid.
Check the range #
e.g. Input # 001 –
128.
004 Incompatible
Feature Set #
Panel’s Feature
Set needs
upgrading.
005 - 019
Future use.
020 - 029
Critical Error
Notify dealer if
persistent.