Monitor xL™ Advanced Installation Guide

21-3602E rev1.5

A0xx02 Keypad Selections
Note: “xx” represents the area number.
(left to right on keypad screen) Example:



Default Name

Selections

Description

0

Exit Delay Warning
Type

0 = Normal, 1=
Warning tone during
Exit Delay, 2=
Warning continuous
3= Warning
continuous + Block
arming

(UK ACPO, European =3)

2

Pre-Alarm Delay

0=20sec; 1=30s;
2=60s; 3=5min;
4=10m; 5=30m;
6=1hr; 7=1.5hrs

During the delay, keypad sonalert(s) will be sounded, giving
an authorized user time to "Silence" the alarm at a keypad.
(Selecting "Verify User" will cancel the alarm transmission.)
Note: This setting works only with sensors (input-points)
that support "Pre-Alarm Warning". For details, refer to
"T080 – T099 (Custom Input-Point Types)".

0

Report Mode

0 = Emergency
1= Full Reporting

System signals transmitted by system dialer to monitoring
station.

0

Siren Squawk on
Arming

0 = Normal, 1=On
Arming, 2 = Fail to
Arm, 3 = On Arming
Or Fail to Arm

The 'siren' outputs for this area will be pulsed briefly when
the area is armed to indicate arming was successful.

(UK ACPO, European =2)

(no)

Function Key PIN
Required

(yes)

(no)

Whether a user with "Function Key" authority will need
to log in to use programmable function-keys 6

9 & 0.

(no)

Dual Custody

(yes)

(no)

Two valid user ID / PINs needed to disarm this area.

(no)

Open Inter-lock Area

(yes)

(no)

For all areas set to Yes, only one area can be
disarmed at a time.

(no)

Auto Arm on Door
Close

(yes)

(no)

Area will arm when any door closes (used with a bank
vault door).

(no)

Suite Security Area

(yes)

(no)

0

·

2

·

0

·

0

·



···

Save A001