C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
66
input
C-PRO
MEGA
RACK;
Visibility *¹
Hd81
Fan 1 thermal DI
pos.
Sets the position of the fan 1
thermal alarm digital input
0
0
12 (22)
CO-Hw
Max =10(18)
on C-PRO
MEGA RACK;
Visibility
*²
Hd82
Fan 2 thermal DI
pos.
Sets the position of the fan 2
thermal alarm digital input
0
0
12 (22)
CO-Hw
Max =10(18)
on C-PRO
MEGA RACK;
Visibility
*²
Hd83
Fan 3 thermal DI
pos.
Sets the position of the fan 3
thermal alarm digital input
0
0
12 (22)
CO-Hw
Max =10(18)
on C-PRO
MEGA RACK;
Visibility
*²
Hd84
Fan 4 thermal DI
pos.
Sets the position of the fan 4
thermal alarm digital input
0
0
12 (22)
CO-Hw
Max =10(18)
on C-PRO
MEGA RACK;
Visibility
*²
Hd85
Fan 5 thermal DI
pos.
Sets the position of the fan 5
thermal alarm digital input
0
0
12 (22)
CO-Hw
Max =10(18)
on C-PRO
MEGA RACK;
Visibility
*²