EVCO c-pro mega RACK User Manual
Page 43

C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
43
PC04
TMinOn
Minimum time for which
the compressor must remain
on, even if switching off
requested
10
0
999
Sec
IS-C
PC05
TMinOff
Minimum time for which
the compressor must remain
off, even if switching on
requested
120
0
999
Sec
IS-C
PC06
TOnOn
Minimum time that must
elapse before the same
compressor can be switched
on.
360
0
999
Sec
IS-C
PC07
TOnOther
Minimum time that must
elapse before another
compressor can be switched
on
20
0
999
Sec
IS-C
PC08
TOffOther
Minimum time that must
elapse before another
compressor can be switched
off
20
0
999
Sec
IS-C
PC09
TOnParz
Minimum time between
switching on of increments
20
0
999
Sec
IS-C
PC10
TOffParz
Minimum time between
switching off of increments
20
0
999
Sec
IS-C
PC11
Comp. probe
error Circuit 1
Number of compressors that
will be forced if an alarm
occurs on the circuit 1
suction probe
1
0
PG11
IS-C
PC31
Comp. probe
error Circuit 2
Number of compressors that
will be forced if an alarm
occurs on the circuit 2
suction probe
1
0
PG15
IS-C
Visible if PG01
> 1
PC51
Comp. probe
error Circuit 3
Number of compressors that
will be forced if an alarm
occurs on the circuit 3
suction probe
1
0
PG21
IS-C
Visible if PG01
> 2
PC69
TRestart
Minimum compressor
switch on wait time
following a system
reset/black-out
0
0
999
Sec
IS-C
PC70
Enable HP
prevention
Enable compressor
increments at high pressure
0: NO
1: YES
0 (NO)
0 (NO)
1 (SI)
IS-C
PC71
HP prevention
C1 limit SP
Set compressor increment
pressure (circuit 1)
22.0
PH03
PH04
Bar
IS-C
PC72
HP prevention
C2 limit SP
Set compressor increment
pressure (circuit 2)
22.0
PH03
PH04
Bar
IS-C
Visible if PG01
> 1