EVCO c-pro mega RACK User Manual
Page 52

C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
52
PA01
Enable
compressor
operation time
alarm
Enables the alarm pertaining
to compressor operation
times
NO
NO (0)
YES (1)
IS-S
PA02
Enable fan
operation time
alarm
Enables the alarm pertaining
to fan operation times
NO
NO (0)
YES (1)
IS-S
PA03
HP suction alarm
delay
Sets the suction high
pressure alarm activation
delay
30
0
999
Sec
IS-S
PA04
ExPro alarm
delay
Sets the expansion unit
alarm activation delay
1
0
999
Sec
IS-S
Only in
versions with
expansion unit
PA05
Fluid level alarm
delay
Sets the fluid level alarm
activation delay
90
0
999
Sec
IS-S
PA06
Probe alarm
delay
Sets the suction and supply
alarm signalling delay
5
0
240
Sec
IS-S
PA07
Supply LP alarm
delay
Sets the supply low pressure
alarm activation delay
30
0
999
Sec
IS-S
PA08
LP suction alarm
delay
Sets the suction low
pressure alarm activation
delay
30
0
999
Sec
IS-S
PA09
Comp. thermal
alarm delay
Sets the compressor thermal
alarm activation delay
0
0
999
Sec
IS-S
PA10
Oil differential
alarm delay
Sets the common oil
differential and compressor
alarm activation delay
10
0
999
Sec
IS-S
PA11
Supply pressure
switch alarm
reset
Sets the type of reset for the
supply pressure-switch
alarm
M
A (0)
M (1)
IS-S
M:manual
A: automatic
PA12
Comp. thermal
alarm reset
Sets the compressor thermal
alarm reset type
M
A (0)
M (1)
IS-S
M: manual
A: automatic
PA13
Comp. pressure-
switch alarm
reset
Sets the compressor
pressure-switch alarm reset
type
M
A (0)
M (1)
IS-S
M: manual
A: automatic
PA14
Oil diff. alarm
reset
Sets the compressor oil
differential alarm reset type
.
M
A (0)
M (1)
IS-S
M: manual
A: automatic
PA23
Fan thermal
alarm reset
Sets the fan thermal alarm
reset type
M
A (0)
M (1)
IS-S
M: manual
A: automatic
PA15
C1 suction LP
alarm setpoint
Circuit 1 suction probe low
pressure alarm setpoint
0.5
PH01
PA17
Bar
IS-S
PA16
C1 suction LP
alarm diff.
Circuit 1 suction probe low
pressure alarm differential
0.5
0.0
20.0
Bar
IS-S
PA17
C1 suction HP
alarm setpoint
Circuit 1 suction probe high
pressure alarm setpoint
4.0
PA15
PH02
Bar
IS-S
PA18
C1 suction HP
alarm diff.
Circuit 1 suction probe high
pressure alarm differential
0.5
0.0
20.0
Bar
IS-S
PA19
C1 supply LP
alarm setpoint
Circuit 1 supply probe low
pressure alarm setpoint
2.0
PH03
PA21
Bar
IS-S
PA20
C1 supply LP
alarm diff.
Circuit 1 supply probe low
pressure alarm differential
0.5
0.0
20.0
Bar
IS-S
PA21
C1 supply HP
alarm setpoint
Circuit 1 supply probe high
pressure alarm setpoint
20.0
PA19
PH04
Bar
IS-S
PA22
C1 supply HP
alarm diff.
Circuit 1 supply probe high
pressure alarm differential
1.0
0.0
20.0
Bar
IS-S
PA25
C2 suction LP
alarm setpoint
Circuit 2 suction probe low
pressure alarm setpoint
0.5
PH01
PA27
Bar
IS-S
Visible if PG01
> 1
PA26
C2 suction LP
Circuit 2 suction probe low
0.5
0.0
20.0
Bar
IS-S
Visible if PG01