EVCO c-pro mega RACK User Manual
Page 54

C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
54
PA39
C3 supply LP
alarm setpoint
Circuit 3 supply probe low
pressure alarm setpoint
2.0
PH03
PA41
Bar
IS-S
Visible if PG01
> 2 and PG30 =
0
PA40
C3 supply LP
alarm diff.
Circuit 3 supply probe low
pressure alarm differential
0.5
0.0
20.0
Bar
IS-S
Visible if PG01
> 2 and PG30 =
0
PA41
C3 supply HP
alarm setpoint
Circuit 3 supply probe high
pressure alarm setpoint
20.0
PA39
PH04
Bar
IS-S
Visible if PG01
> 2 and PG30 =
0
PA42
C3 supply HP
alarm diff.
Circuit 3 supply probe high
pressure alarm differential
1.0
0.0
20.0
Bar
IS-S
Visible if PG01
> 2 and PG30 =
0
PH16
Compressor
safety device
type
Sets the type of safety
devices used for the
compressors:
0: None
1: Thermal
2: Thermal + pressure-
switch
3: Thermal + oil diff.
4: All
Thermal
None (0)
All (4)
IS-S
SYSTEM BUILDER MENU PARAMETERS
PG01
Circuit number
Sets the number of circuits
for the machine
2
1
3
CO-W
Default = 1
on C-PRO
MEGA RACK
PG02
Enable
expansion
Enables the expansion unit
and the corresponding
alarms
NO
NO (0)
YES (1)
CO-W
PG03
Enable
differently
powered
compressors
Enables the management of
compressors with different
nominal power ratings
NO
NO (0)
YES (1)
CO-W
PG04
Number of
increments per
compressor
Sets the number of
increments for each
compressor
1
0
3
CO-W
Default = 0
on C-PRO
MEGA RACK
PG05
Number of safety
devices per
compressor
Sets the number of safety
devices for each compressor
1
0
3
CO-W
PG11
Number of
compressors for
Circuit 1
Sets the number of
compressors for circuit 1
2
0
12
CO-W
Default = 4
Max = 8
on C-PRO
MEGA RACK
PG12
Circuit 1 inverter
comp. enable
Enables the compressor
with circuit 1 inverter
NO
NO (0)
YES (0)
CO-W
PG15
Number of
compressors for
Circuit 2
Sets the number of
compressors for circuit 2
2
0
12
CO-W
Default = 0
Max = 8
on C-PRO
MEGA RACK;
Visible if PG01
> 1
PG16
Circuit 2 inverter
comp. enable
Enables the compressor
with circuit 2 inverter
NO
NO (0)
YES (0)
CO-W
Visible if PG01
> 1
PG21
Number of
compressors for
Circuit 3
Sets the number of
compressors for circuit 3
0
0
12
CO-W
Max = 8
on C-PRO
MEGA RACK;
Visible if PG01
> 2