3 alarm relays – EVCO c-pro mega RACK User Manual
Page 104

C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
104
ACC1
C1 common oil differential
Settable
Display
Configurable delay
AFC1
C1 common fan thermal
Manual
Display
AL32
C2 supply pressure high
Auto
All fans ON
AL37
C2 suction pressure high
Auto
All comp. ON
Configurable delay
AL42
C2 supply pressure low
Auto
All fans OFF
- Configurable delay
- Only present if the
circuit is on
AL47
C2 suction pressure low
Auto
All comp. OFF
- Configurable delay
- Only present if the
circuit is on
AL12
C2 supply high pressure pressure-switch
Settable
All comp. OFF
AL22
C2 suction low pressure pressure-switch
Auto
All comp. OFF
Only present if the
circuit is on
AL62
C2 fluid level
Manual
Display
Configurable delay
ACC2
C2 common oil differential
Settable
Display
AFC2
C2 common fan thermal
Manual
Display
AL33
C3 supply pressure high
Auto
All fans ON
AL38
C3 suction pressure high
Auto
All comp. ON
Configurable delay
AL43
C3 supply pressure low
Auto
All fans OFF
- Configurable delay
- Only present if the
circuit is on
AL48
C3 suction pressure low
Auto
All comp. OFF
- Configurable delay
- Only present if the
circuit is on
AL13
C3 supply high pressure pressure-switch
Settable
All comp. OFF
AL23
C3 suction low pressure pressure-switch
Auto
All comp. OFF
Only present if the
circuit is on
AL63
C3 fluid level
Manual
Display
Configurable delay
ACC3
C3 common oil differential
Settable
Display
Configurable delay
AFC3
C3 common fan thermal
Manual
Display
ES07
Faulty or disconnected environment probe
Auto
Display
ES08
Faulty or disconnected external probe
Auto
Floating condensation
OFF
AH01
Hardware configuration error
Auto
Display
Appears when the
wizard attempts to
set a hardware
configuration not
attainable with the
available hardware
resources
(
*
¹) To reset alarms due to compressor/fan operating times it is necessary to zero the operating time
for the relevant device from the service menu. Once the times have been zeroed, the alarms relating
to the compressors/fans will be reset automatically.
7.3
Alarm relays
The program has the capacity to manage up to four alarm relays. Each alarm is enabled depending
on whether or not the relevant parameter, Alarm DO position, has been set. To enable, simply set
this to a value other than zero, if the value remains at zero, the alarm relay is not used.
The four relays, with relevant parameters, are listed below:
⋅
General alarm relay - Global alarm DO position
⋅
Circuit 1 alarm relay - Circuit 1 alarm DO position
⋅
Circuit 2 alarm relay - Circuit 2 alarm DO position
⋅
Circuit 3 alarm relay - Circuit 3 alarm DO position