EVCO c-pro mega RACK User Manual
Page 18

C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
18
JMP3
CAN terminator
Jumper not inserted
Termination (120
?
) not inserted
Jumper inserted
Termination (120
?
) inserted
JMP4
Local CAN serial port baud rate selection
A
B
Jumper A inserted
Jumper B inserted
Baud rate = 20K
A
B
Jumper A inserted
Jumper B not inserted
Baud rate = 50K
A
B
Jumper A not inserted
Jumper B inserted
Baud rate = 125K
A
B
Jumper A not inserted
Jumper B not inserted
Baud rate = 500K
JMP5
RS-485 terminator
Jumper not inserted
Termination (120
?
) not inserted
Jumper inserted
Termination (120
?
) inserted
JMP6
Analogue output selection
A
B
C
D
Jumper A inserted
Jumper B inserted
Jumper C inserted
Jumper D inserted
Output AO1 under current
Output AO2 under current
Output AO3 under current
Output AO4 under current
A
B
C
D
Jumper A not inserted
Jumper B not inserted
Jumper C not inserted
Jumper D not inserted
Output AO1 under tension
Output AO2 under tension
Output AO3 under tension
Output AO4 under tension
PLEASE NOTE:
It is not sufficient to merely set the jumper to configure the signal distributed by the analogue
output, the controller machine parameters must also be set (see the chapter “Configuration of the
signal distributed by the analogue output” in the Hardware Manual).