EVCO c-pro mega RACK User Manual
Page 37

C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
37
PUF2
Fan secondary
setpoint offset
Circuit 2
Sets the offset value for use
of secondary setpoint from
fan digital input
0.0
-20.0
20.0
Bar
UT
Visible if PG01
> 1 and
PG30 = 0
PUF5
Fan sup.
secondary
setpoint offset
Circuit 2
Sets the offset value for use
of secondary setpoint from
fan supervisor
0.0
-20.0
20.0
Bar
UT
Visible if PG01
> 1 and
PG30 = 0
SPF3
Fan setpoint
Circuit 3
Sets the setpoint value for
the fan supply probe
15.0
PF52
PF53
Bar
UT
Visible if PG01
> 2 and
PG30 = 0
PUF3
Fan secondary
setpoint offset
Circuit 3
Sets the offset value for use
of secondary setpoint from
fan digital input
0.0
-20.0
20.0
Bar
UT
Visible if PG01
> 2 and
PG30 = 0
PUF6
Fan sup.
secondary
setpoint offset
Circuit 3
Sets the offset value for use
of secondary setpoint from
fan supervisor
0.0
-20.0
20.0
Bar
UT
Visible if PG01
> 2 and
PG30 = 0
PSd1
User PSd
User level password
0
-999
9999
UT
SERVICE MENU PARAMETERS
PM00
Compressor
operational time
alarm threshold
Sets the maximum
compressor operation time
limit. Beyond this limit, the
relevant alarm will be
tripped
20000
0
500000
Hou
rs
MA-F
PM01..10
Compressor
operation
time (1..10)
Operation times for each
compressor
0
0
500000
Hou
rs
MA-F
Compressors 1
to 10;
Visibility
*¹
PM31
PM32
Compressor
operation
time (11-12)
Operation times for each
compressor
0
0
500000
Hou
rs
MA-F
Compressors
11 and 12;
Visibility
*¹
PM40
Fan operational
time alarm
threshold
Sets the maximum fan
operation time limit.
Beyond this limit, the
relevant alarm will be
tripped
20000
0
500000
Hou
rs
MA-F
PM41..50
Fan operation
time (1..10)
Operation times for each fan
0
0
500000
Hou
rs
MA-F
Fans 1 to 10;
Visibility
*²
PM71
PM72
Fan operation
time (11-12)
Operation times for each fan
0
0
500000
Hou
rs
MA-F
Fans 11 and 12;
Visibility
*²
PM90
Last maintenance
date
Sets the last date on which
system maintenance was
carried out
MA-F
PSd2
Service PSd
Service level password
0
-999
9999
MA-F
PM11..20
Enable
compressor
(1..10)
Enables manual/automatic
operation of each
compressor:
M: manual
A: normal operation
A
A (0)
M (1)
MA-M
Compressors 1
to 10; Visibility
*¹