EVCO c-pro mega RACK User Manual
Page 51

C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
51
PH36
Suction load
compensation
offset
Load loss compensation
factor
0.2
0.1
5.0
Bar
IS-V
PH40
Measurement
unit
Sets the display for
temperature or pressure
0: Pressure
1: Temperature
0
(Pres.)
0
(Pres.)
1
(Temp.)
IS-V
PH43
AI1 probe type
Sets the type of AI01
analogue input:
2: NTC
3: 0-20mA
4: 4-20mA
4
4-20mA
2
4
IS-V
PH44
AI2 probe type
Sets the type of AI02
analogue input:
2: NTC
3: 0-20mA
4: 4-20mA
4
4-20mA
2
4
IS-V
PH45
AI3_4 probe
type
Sets analogue input type for
AI03 and AI04:
2: NTC
3: 0-20mA
4: 4-20mA
4
4-20mA
2
4
IS-V
Visible if
PG01 > 1
PH47
AI5_6 probe
type
Sets analogue input type for
AI05 and AI06:
2: NTC
3: 0-20mA
4: 4-20mA
4
4-20mA
2
4
IS-V
Visible if
PG01 > 2
PH53
Buzzer enable
Enables the buzzer to sound
YES (1)
NO (0)
YES (1)
IS-V
PSd3
Installer PSd
Installer level password
0
-999
9999
IS-V
ALARM PARAMETERS
PH17
DI alarm logic
Sets the digital input alarm
logic used for controlling
the alarms:
0: Normally open NO
1: Normally closed NC
NC
NO (0)
NC (1)
IS-S
PH18
DO alarm logic
Sets the logic for the relays
used for the alarms
0: Normally open NO
1: Normally closed NC
NO
NO (0)
NC (1)
IS-S
PH19
Other DI logic
Sets the digital input alarm
logic used for controlling
the following functions:
- Global remote OnOff
- Circuit remote OnOff
- compressor/fan secondary
setpoint
0: Normally open NO
1: Normally closed NC
NO
NO (0)
NC (1)
IS-S