C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
41
Circuit 2
the minimum value to the
maximum value ( circuit 2
neutral zone reg.)
1
PC52
Compressor min.
setpoint
Circuit 3
Minimum suction setpoint
value pertaining to the
compressors of circuit 3
0.1
PH01
SPC3
Bar
IS-RC
Visible if PG01
> 2
PC53
Compressor
max. setpoint
Circuit 3
Maximum suction setpoint
value pertaining to the
compressors of circuit 3
2.5
SPC3
PH02
Bar
IS-RC
Visible if PG01
> 2
PC54
Compressor
regulation
Circuit 3
Sets the type of regulation
for controlling the circuit 3
compressors
Neutral
Zone (1)
Side
Band (0)
Neutral
Zone (1)
IS-RC
Visible if PG01
> 2
PC56
Compressor
integral time
Circuit 3
Integral time Ti for side
band regulation of circuit 3
compressors
600
0
999
Sec
IS-RC
Visible if PG01
> 2 and
PC54 = 0
PC57
Compressor
proportional
band. Circuit 3
Proportional band Bp for
side band regulation of
circuit 3 compressors
0.5
0
20.0
Bar
IS-RC
Visible if PG01
> 2 and
PC54 = 0
PC58
Comp. zone
Circuit 3
Zone value for neutral zone
regulation of circuit 3
compressors
0.5
0
20.0
Bar
IS-RC
Visible if PG01
> 2 and
PC54 = 1
PC59
Comp. zone
differential
Circuit 3
Differential, for neutral zone
regulation, within which the
calculation for the
insertion/release time of the
subsequent step varies.
Circuit 3
0.5
0
20.0
Bar
IS-RC
Visible if PG01
> 2 and
PC54 = 1