EVCO c-pro mega RACK User Manual
Page 48

C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
48
PF72
Floating
condensation
offset
Floating condensation
temperature variation offset
0.0
-20.0
20.0
°C
IS-F
PF73
Set floating
condensation
min.
Minimum floating
condensation limit value
30.0
10.0
45.0
°C
IS-F
PF74
Set floating
condensation
max.
Maximum floating
condensation limit value
40.0
10.0
45.0
°C
IS-F
PF78
Side band step
overlap
Fan side band step overlap
factor
0
0
100
%
IS-F
PH01
Minimum full-
scale suction
Sets the minimum full-scale
value for the suction probe
-0.5
-10.0
PH02
Bar
IS-V
PH02
Maximum full-
scale suction
Sets the maximum full-scale
value for the suction probe
7.0
PH01
45.0
Bar
IS-V
PH03
Minimum full-
scale supply
Sets the minimum full-scale
value for the supply probe
0.0
-10.0
PH04
Bar
IS-V
PH04
Maximum full-
scale supply
Sets the maximum full-scale
value for the supply probe
30.0
PH03
45.0
Bar
IS-V
PH05
System ON/OFF
from keypad
Enables switching the
machine on/off by pressing
the ESC key
YES
NO (0)
YES (1)
IS-V
PH06
Circuit ON/OFF
from keypad
Enables switching circuits
on/off by pressing the
relevant key
NO
NO (0)
YES (1)
IS-V
PH07
System ON/OFF
from DI
Enables switching the
machine on/off from the
digital input
NO
NO (0)
YES (1)
IS-V
PH08
Circuits ON/OFF
from DI
Enables switching circuits
on/off from the relevant
digital input
NO
NO (0)
YES (1)
IS-V
PH09
System ON/OFF
from supervisor
Enables switching the
machine on/off from the
supervisor
NO
NO (0)
YES (1)
IS-V
PH10
Circuits ON/OFF
from supervisor
Enables switching circuits
on/off from the supervisor
NO
NO (0)
YES (1)
IS-V
PH11
Modbus address
Card Modbus address
1
1
247
IS-V