C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
40
offset. Circuit 1
of the compressor.
PC26
Inverter comp.
min. Circuit 1
Minimum compressor value
with circuit 1 inverter
0.0
0.0
100.0
%
IS-RC
Visible if PG12
= 1
PC27
Inverter comp.
speedup
Circuit 1
Compressor speedup time
with circuit 1 inverter
0
0
999
Sec
IS-RC
Visible if PG12
= 1
PC28
Inverter
compressor time
Circuit 1
Inverter ramp. Time taken
for the inverter to go from
the minimum value to the
maximum value ( circuit 1
neutral zone reg.)
10
0
999
Sec
IS-RC
Visible if PG12
= 1
PC32
Compressor min.
setpoint
Circuit 2
Minimum suction setpoint
value pertaining to the
compressors of circuit 2
0.1
PH01
SPC2
Bar
IS-RC
Visible if PG01
> 1
PC33
Compressor
max. setpoint
Circuit 2
Maximum suction setpoint
value pertaining to the
compressors of circuit 2
2.5
SPC2
PH02
Bar
IS-RC
Visible if PG01
> 1
PC34
Compressor
regulation
Circuit 2
Sets the type of regulation
for controlling the circuit 2
compressors
Neutral
Zone (1)
Side
Band (0)
Neutral
Zone (1)
IS-RC
Visible if PG01
> 1
PC36
Compressor
integral time
Circuit 2
Integral time Ti for side
band regulation of circuit 2
compressors
600
0
999
Sec
IS-RC
Visible if PG01
> 1 and PG34 =
0
PC37
Compressor
proportional
band. Circuit 2
Proportional band Bp for
side band regulation of
circuit 2 compressors
0.5
0
20.0
Bar
IS-RC
Visible if PG01
> 1 and PG34 =
0
PC38
Comp. zone
Circuit 2
Zone value for neutral zone
regulation of circuit 2
compressors
0.5
0
20.0
Bar
IS-RC
Visible if PG01
> 1 and PG34 =
1
PC39
Comp. zone
differential
Circuit 2
Differential, for neutral zone
regulation, within which the
calculation for the
insertion/release time of the
subsequent step varies.
Circuit 2
0.5
0
20.0
Bar
IS-RC
Visible if PG01
> 1 and PG34 =
1
PC40
Compressor
TOnMin
Circuit 2
Minimum insertion time for
subsequent compressor step
( circuit 2 neutral zone reg.)
20
0
PC41
Sec
IS-RC
Visible if PG01
> 1 and PG34 =
1
PC41
Compressor
TOnMax
Circuit 2
Maximum insertion time for
subsequent compressor step
( circuit 2 neutral zone reg.)
60
PC40
999
Sec
IS-RC
Visible if PG01
> 1 and PG34 =
1
PC42
Compressor
TOffMin
Circuit 2
Minimum release time for
subsequent compressor step
( circuit 2 neutral zone reg.)
10
0
PC43
Sec
IS-RC
Visible if PG01
> 1 and PG34 =
1
PC43
Compressor
TOffMax
Circuit 2
Maximum release time for
subsequent compressor step
( circuit 2 neutral zone reg.)
60
PC42
999
Sec
IS-RC
Visible if PG01
> 1 and PG34 =
1
PC44
Comp. inverter
diff.
Circuit 2
Differential for compressor
regulation with circuit 2
inverter
0.5
0.0
20.0
Bar
IS-RC
Visible if PG01
> 1 and PG16 =
1
PC45
Compressor
inverter SP
offset. Circuit 2
Suction setpoint offset for
circuit 2 inverter regulation
of the compressor.
0.0
-20.0
20.0
Bar
IS-RC
Visible if PG01
> 1 and PG16 =
1
PC46
Inverter comp.
min. Circuit 2
Minimum compressor value
with circuit 2 inverter
0.0
0.0
100.0
%
IS-RC
Visible if PG01
> 1 and PG16 =
1
PC47
Inverter comp.
speedup
Circuit 2
Compressor speedup time
with circuit 2 inverter
0
0
999
Sec
IS-RC
Visible if PG01
> 1 and PG16 =
1
PC48
Inverter
compressor time
Inverter ramp. Time taken
for the inverter to go from
10
0
999
Sec
IS-RC
Visible if PG01
> 1 and PG16 =