C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
42
PC60
Compressor
TOnMin
Circuit 3
Minimum insertion time for
subsequent compressor step
( circuit 3 neutral zone reg.)
20
0
PC61
Sec
IS-RC
Visible if PG01
> 2 and
PC54 = 1
PC61
Compressor
TOnMax
Circuit 3
Maximum insertion time for
subsequent compressor step
( circuit 3 neutral zone reg.)
60
PC60
999
Sec
IS-RC
Visible if PG01
> 2 and
PC54 = 1
PC62
Compressor
TOffMin
Circuit 3
Minimum release time for
subsequent compressor step
( circuit 3 neutral zone reg.)
10
0
PC63
Sec
IS-RC
Visible if PG01
> 2 and
PC54 = 1
PC63
Compressor
TOffMax
Circuit 3
Maximum release time for
subsequent compressor step
( circuit 3 neutral zone reg.)
60
PC62
999
Sec
IS-RC
Visible if PG01
> 2 and
PC54 = 1
PC64
Comp. inverter
diff.
Circuit 3
Differential for compressor
regulation with circuit 3
inverter
0.5
0.0
20.0
Bar
IS-RC
Visible if PG01
> 2 and
PG22 = 1
PC65
Compressor
inverter SP
offset. Circuit 3
Suction setpoint offset for
circuit 3 inverter regulation
of the compressor.
0.0
-20.0
20.0
Bar
IS-RC
Visible if PG01
> 2 and
PG22 = 1
PC66
Inverter comp.
min. Circuit 3
Minimum compressor value
with circuit 3 inverter
0.0
0.0
100.0
%
IS-RC
Visible if PG01
> 2 and
PG22 = 1
PC67
Inverter comp.
speedup
Circuit 3
Compressor speedup time
with circuit 3 inverter
0
0
999
Sec
IS-RC
Visible if PG01
> 2 and
PG22 = 1
PC68
Inverter
compressor time
Circuit 3
Inverter ramp. Time taken
for the inverter to go from
the minimum value to the
maximum value ( circuit 3
neutral zone reg.)
10
0
999
Sec
IS-RC
Visible if PG01
> 2 and
PG22 = 1
PC01
Compressor
rotation
Type of rotation used for
compressor management:
0: FIFO
1: LIFO
2: FIFO+HR
3: LIFO+HR
FIFO
FIFO (0)
LIFO +
HR (3)
IS-C
PC02
Increment trigger
Sets the increment trigger
mode:
0: CpCp_pCpC
1: CCpp_ppCC
2: CpCp_ppCC
3: CCpp_pCpC
CpCp_pCpC
CpCp_pCpC
(0)
CCpp_pCpC
(3)
IS-C
PC03
Increment logic
Sets the relay logic used for
the compressor increments:
0: NC = normally closed
(e.g. Copeland)
1: NO = normally open (e.g.
Feeders)
NO
NC (0)
NO (1)
IS-C