EVCO c-pro mega RACK User Manual
Page 23

C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
23
2.7.3
Input and output identification tables
Card with 12 VDC power supply
Conn.
Abbre
v.
Description
C1-1
VCC
card power supply input (+13 V DC)
C1-2
GND
power supply reference
JD-1
VDC
active probe power supply (*1)
JD-2
AI1
No.1 configurable analogue input (NTC, 0..20 mA, 4..20 mA)
JD-3
AI2
No.2 configurable analogue input (NTC, 0..20 mA, 4..20 mA)
JD-4
AI3
No.3 configurable analogue input (NTC, 0..20 mA, 4..20 mA)
JD-5
AI4
No.4 configurable analogue input (NTC, 0..20 mA, 4..20 mA)
JD-6
GND
analogue input common ground
JF-1
COM
digital input common connection
JF-2
DI1
No.1 digital input 12-24 VAC/DC
JF-3
DI2
No.2 digital input 12-24 VAC/DC
JF-4
DI3
No.3 digital input 12-24 VAC/DC
JF-5
DI4
No.4 digital input 12-24 VAC/DC
JF-6
COM
digital input common connection
JG-1
COM
digital input common connection
JG-2
DI5
No.5 digital input 12-24 VAC/DC
JG-3
DI6
No.6 digital input 12-24 VAC/DC
JG-4
DI7
No.7 digital input 12-24 VAC/DC
JG-5
DI8
No.8 digital input 12-24 VAC/DC
JG-6
COM
digital input common connection
YA-1
VDC
power supply output connector (12 VDC)
YA-2
CAN1+
connector for connecting the CAN serial port (CAN+)
YA-3
CAN1-
connector for connecting the CAN serial port (CAN-)
YA-4
GND
power supply output reference connector (ground)
JH-1
NC 1
relay No. 1 contact normally closed
JH-2
COM 1
relay No. 1 common connection
JH-3
NO 1
relay No. 1 contact normally open
JI-1
NC 2
relay No. 2 contact normally closed
JI-2
COM 2
relay No. 2 common connection
JI-3
NO 2
relay No. 2 contact normally open
JK-1
COM 3
relay No. 3 common connection
JK-2
NO 3
relay No. 3 contact normally open
JK-3
COM 4
relay No. 4 common connection
JK-4
NO 4
relay No. 4 contact normally open
JK-5
COM 5
relay No. 5 common connection
JK-6
NO 5
relay No. 5 contact normally open
JL-1
COM 6
relay No. 6 common connection
JL-2
NO 6
relay No. 6 contact normally open
JL-3
COM 7
relay No. 7 common connection
JL-4
NO 7
relay No. 7 contact normally open
JL-5
COM 8
relay No. 8 common connection
JL-6
NO 8
relay No. 8 contact normally open
YB
PRG
not used
C2-1
VCC
not used
C2-2
GND
not used