EVCO c-pro mega RACK User Manual
Page 55

C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
55
PG22
Circuit 3 inverter
comp. enable
Enables the compressor
with circuit 3 inverter
NO
NO (0)
SO (0)
CO-W
Visible if PG01
> 2
PG30
Enable unique
condensation
Sets unique condensation
for the fan unit
NO
NO (0)
YES (1)
CO-W
Dual – triple
circuits only
PG32
Fan safety device
Enables the fan thermal
safety device
YES
NO (0)
YES (1)
CO-W
PG41
Number of fans
for Circuit 1
Sets the number of fans for
circuit 1
2
0
12
CO-W
Default = 3
Max = 8
on C-PRO
MEGA RACK
PG42
Circuit 1 fan
inverter enable
Enables the fan with circuit
1 inverter
NO
NO (0)
YES (0)
CO-W
PG45
Number of fans
for Circuit 2
Sets the number of fans for
circuit 2
2
0
12
CO-W
Default = 0
Max = 8
on C-PRO
MEGA RACK;
Visible if PG01
> 1 and PG30 =
0
PG46
Circuit 2 fan
inverter enable
Enables the fan with circuit
2 inverter
NO
NO (0)
YES (0)
CO-W
Visible if PG01
> 1 and PG30 =
0
PG51
Number of fans
for Circuit 3
Sets the number of fans for
circuit 3
0
0
12
CO-W
Max = 8
on C-PRO
MEGA RACK;
Visible if PG01
> 2 and PG30 =
0
PG52
Circuit 3 fan
inverter enable
Enables the fan with circuit
3 inverter
NO
NO (0)
YES (0)
CO-W
Visible if PG01
> 2 and PG30 =
0
PH20
Circuit 1 system
type or control
unit type
Sets the type of control unit
for the first circuit*:
0: -
1: BT
2: TN
3: AT
-
- (0)
AT (3)
CO-Pa
* In the case of
a single circuit
system the
parameter sets
the system type
PH21
Circuit 2 control
unit type
Sets the type of control unit
for the second circuit:
0: -
1: BT
2: TN
3: AT
-
- (0)
AT (3)
CO-Pa
Visible if PG01
> 1
PH22
Circuit 3 control
unit type
Sets the type of control unit
for the third circuit:
0: -
1: BT
2: TN
3: AT
-
- (0)
AT (3)
CO-Pa
Visible if PG01
> 2
PH27
Home page
Selects the home page to be
displayed at machine
startup:
0: Global
1: Circuit1
2: Circuit 2*
3: Circuit 3*
Global
(0)
Global
(0)
Circuit 3
(3)
CO-Pa
* If PH27=2.3
and the relevant
circuit is not
enabled,
assume a
default value of
“0”
PSd4
System builder
PSd
System builder level
password
0
-999
9999
CO-Pa
SYSTEM BUILDER MENU PARAMETERS – Compressor and fan digital output positions