C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
36
Circuit 1
time bands. Circuit 1
PT71..74
Fan time band
offset (1..4)
Circuit 2
Sets the offsets to the fan
setpoints in relation to the 4
time bands. Circuit 2
0.0
PF32
PF33
Bar
OR
Visible if PG01
> 1 and
PG30 = 0
PT81..84
Fan time band
offset (1..4)
Circuit 3
Sets the offsets to the fan
setpoints in relation to the 4
time bands. Circuit 3
0.0
PF52
PF53
Bar
OR
Visible if PG01
> 2 and
PG30 = 0
USER MENU PARAMETERS
SPC1
Compressor
setpoint
Circuit 1
Sets the setpoint value for
the compressor suction
probe
1.0
PC12
PC13
Bar
UT
PUC1
Comp. DI
secondary
setpoint offset
Circuit 1
Sets the offset value for use
of secondary setpoint from
the compressor digital input
0.0
-20.0
20.0
Bar
UT
PUC4
Comp. sup.
Secondary
setpoint offset
Circuit 1
Sets the offset value for use
of secondary setpoint from
compressor supervisor
0.0
-20.0
20.0
Bar
UT
SPC2
Compressor
setpoint
Circuit 2
Sets the setpoint value for
the compressor suction
probe
1.0
PC32
PC33
Bar
UT
Visible if PG01
> 1
PUC2
Comp. DI
secondary
setpoint offset
Circuit 2
Sets the offset value for use
of secondary setpoint from
the compressor digital input
0.0
-20.0
20.0
Bar
UT
Visible if PG01
> 1
PUC5
Comp. sup.
Secondary
setpoint offset
Circuit 2
Sets the offset value for use
of secondary setpoint from
compressor supervisor
0.0
-20.0
20.0
Bar
UT
Visible if PG01
> 1
SPC3
Compressor
setpoint
Circuit 3
Sets the setpoint value for
the compressor suction
probe
1.0
PC52
PC53
Bar
UT
Visible if PG01
> 2
PUC3
Comp. DI
secondary
setpoint offset
Circuit 3
Sets the offset value for use
of secondary setpoint from
the compressor digital input
0.0
-20.0
20.0
Bar
UT
Visible if PG01
> 2
PUC6
Comp. sup.
Secondary
setpoint offset
Circuit 3
Sets the offset value for use
of secondary setpoint from
compressor supervisor
0.0
-20.0
20.0
Bar
UT
Visible if PG01
> 2
SPF1
Fan setpoint
Circuit 1
Sets the setpoint value for
the fan supply probe
15.0
PF12
PF13
Bar
UT
PUF1
Fan secondary
setpoint offset
Circuit 1
Sets the offset value for use
of secondary setpoint from
fan digital input
0.0
-20.0
20.0
Bar
UT
PUF4
Fan sup.
secondary
setpoint offset
Circuit 1
Sets the offset value for use
of secondary setpoint from
fan supervisor
0.0
-20.0
20.0
Bar
UT
SPF2
Fan setpoint
Circuit 2
Sets the setpoint value for
the fan supply probe
15.0
PF32
PF33
Bar
UT
Visible if PG01
> 1 and
PG30 = 0