beautypg.com

EVCO EPV4CBR Hardware manual User Manual

Page 35

background image

EVCO S.p.A.

Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104

page 35 of 38

Power supply:

-

24 VAC (±15%), 50 / 60 Hz (±3 Hz), 3 VA max not isolated

-

24 VDC (-15%, +65%), 2 W max not isolated

supplied by a class 2 circuit.

Protect the power supply by one of the following fuses:

-

160 mA-T if the device is powered in alternating current

-

80 mA-T if the device is powered in direct current.

If the device is powered in direct current, it will be necessary to respect the polarity of the

power supply voltage.

The power supply must galvanically be isolated by those of the other elements of the RS-485

network with MODBUS communication protocol or the CAN network with CANBUS

communication protocol.

Rated impulse voltage:

4 KV.

Overvoltage category:

III.

Software class:

A.

Real time clock:

incorporated (SuperCap).

Data maintenance in case of absence of the power supply: 24 h with battery full loaded.

Battery loading time: 2 min (the battery is loaded by the power supply of the device).

Type 1 or type 2 actions:

Type 1.

Features of actions type 1 or

type 2:

C.

Display:

320 x 240 pixel color resistive touch-screen TFT graphic display.

Communication ports:

3 ports:

-

1 RS-485 port with MODBUS communication protocol

-

1 CAN port with CANBUS communication protocol

-

1 USB port.

Alarm buzzer:

incorporated.