EVCO EPV4CBR Hardware manual User Manual

Page 29

background image

EVCO S.p.A.

Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104

page 29 of 38

7.7.5

Configuration parameters of the submenu “UART” of the menu “Networks”

The following table shows the meaning of the configuration parameters of the submenu “UART” of the menu “Networks”.

PARAM.

MIN.

MAX.

U.M.

DEF.

DESCRIPTION

Address

1

247

- - -

1

MODBUS address of the device (meaningful if the communication

protocol is MODBUS slave)

Parity

- - -

- - -

- - -

even

parity of the MODBUS communication

none =

none

odd =

odd

even =

even

Baudrate

- - -

- - -

- - -

9600

baud rate of the MODBUS communication

1200 =

1,200

baud

2400 =

2,400

baud

4800 =

4,800

baud

9600 =

9,600

baud

19200 =

19,200

baud

28800 =

28,800

baud

38400 =

38,400

baud

57600 =

57,600

baud

Bit Stop

- - -

- - -

- - -

1 bit

number of stop bit of the MODBUS communication

1 bit

= 1 bit

2 bit

= 2 bit

Timeout

2 240 s

10

time-out of the local MODBUS communication, or of the device

(once the time you have set with this parameter has elapsed from

the transmission of a request without answer, the transmission of

the request is considered failed and the following request is

transmitted; meaningful if the communication protocol is

MODBUS master)

7.7.6

Configuration parameters of the submenu “USB” of the menu “Networks”

The following table shows the meaning of the configuration parameters of the submenu “USB” of the menu “Networks”.

PARAM.

MIN.

MAX.

U.M.

DEF.

DESCRIPTION

USB Status

Device

parameter available in read only mode

reserved

Device

Status Idle

Speed

parameter available in read only mode

reserved