EVCO EVB1256N9D User Manual
Page 87

EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 87 of 92
Humidity for use:
from 10 to 90 % relative humidity without condensate.
Command device pollution situation:
2.
Height at which it is used:
from 0 to 2,000 m (from 0 to 6,591 ft).
Height at which it can be transported:
from 0 to 3,048 m (from 0 to 10,000 ft).
Environmental standards:
-
RoHS 2011/65/CE
-
WEEE 2012/19/EU
-
REACH (CE) regulation n. 1907/2006.
EMC standards:
-
EN 60730-1
-
IEC 60730-1.
Power supply:
115... 230 VAC (+10 %, -15 %), 50/60 Hz (±3 Hz), 35 VA max.
non insulated, supplied by a class 2 circuit.
The maximum phase current allowed is 16 A.
Magneto-thermal switch:
according to model (230 VAC, In 16 A, Icn 4.500 A, unipolar +
neutral, for wires up to 2,5 mm² (0.0387 in²).
Differential magneto-thermal circuit breaker:
according to model (230 VAC, In 16 A, Icn 4.500 A, Id 300 mA,
unipolar + neutral, for wires up to 2,5 mm² (0.0387 in²).
Remote control switch for three-phase defrost elements
management:
according to model (230 VAC, Ie 9 A, Ui 690 V, Uimp 6 KV, Ith
20 A, 2,2 KW in AC3 at 230 VAC with ta 55 °C, three poles +
neutral, for wires up to 2,5 mm² (0,0387 in²).
Control device grounding method:
with ground terminal
Rated impulse voltage:
4 KV.
Overvoltage category:
III.
Class and structure of software:
A.
Real time clock:
incorporated (with lithium secondary battery).
Battery autonomy without power supply: 6 months.
Battery recharging time: 24 h (the battery is recharged through
the device power supply).
Drift: ≤ 30 s/month at 25 °C (77 °F).