EVCO EVB1256N9D User Manual
Page 53

EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 53 of 92
d21
0
500
min
200
200
200
200
200
200
200
200
minimum consecutive time the compressor must be
switched on after the insturment switches on (on
condition that the difference “cell temperature - working
setpoint” is higher than 10 °C/20 °F) and after function
Overcooling is activated such as to provoke the defrost
activation
0
=
the defrost will never be activated because the
compressor has been switched on
d22
0.0
10.0
°C/°F
(1)
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
evaporator temperature above which the time d18 count
is paused (relating to the average of evaporator
temperatures, that is to say, "evaporator temperatures
average + d22”) (only if d8 = 3)
d25
0
1
- - - -
0
0
0
0
0
0
0
0
enabling of the outlet air temperature probe as defrosting
probe during the evaporator temperature probe error
(code “Pr2”; only if P4 = 4); see also d26 (19)
d26
0
99
h
6
6
6
6
6
6
6
6
defrosting interval for effect of enabling of outlet air
temperature probe like defrosting probe during evaporator
temperature probe error (code “Pr2”; only if P4 = 4), if
d25 = 1 (13)
0
=
defrosting will never be activated due to the effect
of this condition