EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134

page 53 of 92

d21

0

500

min

200

200

200

200

200

200

200

200

minimum consecutive time the compressor must be

switched on after the insturment switches on (on

condition that the difference “cell temperature - working

setpoint” is higher than 10 °C/20 °F) and after function

Overcooling is activated such as to provoke the defrost

activation

0

=

the defrost will never be activated because the

compressor has been switched on

d22

0.0

10.0

°C/°F

(1)

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

evaporator temperature above which the time d18 count

is paused (relating to the average of evaporator

temperatures, that is to say, "evaporator temperatures

average + d22”) (only if d8 = 3)

d25

0

1

- - - -

0

0

0

0

0

0

0

0

enabling of the outlet air temperature probe as defrosting

probe during the evaporator temperature probe error

(code “Pr2”; only if P4 = 4); see also d26 (19)

d26

0

99

h

6

6

6

6

6

6

6

6

defrosting interval for effect of enabling of outlet air

temperature probe like defrosting probe during evaporator

temperature probe error (code “Pr2”; only if P4 = 4), if

d25 = 1 (13)

0

=

defrosting will never be activated due to the effect

of this condition