EVCO EVB1256N9D User Manual
Page 73

EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 73 of 92
PARAM.
MIN.
MAX.
M.U.
E
V
B
1
2
0
4
E
V
B
1
2
1
4
E
V
B
1
2
0
6
E
V
B
1
2
1
6
E
V
B
1
2
2
6
E
V
B
1
2
3
6
E
V
B
1
2
4
6
E
V
B
1
2
5
6
RS-485 MODBUS
LA
1
247
- - - -
247
247
247
247
247
247
247
247
device address
Lb
0
3
- - - -
2
2
2
2
2
2
2
2
baud rate
0
=
2.400 baud
1
=
4.800 baud
2
=
9.600 baud
3
=
19.200 baud
LP
0
2
- - -
2
2
2
2
2
2
2
2
parity
0
=
none (no parity)
1
=
odd
2
=
even
Notes:
(1)
the unit of measurement depends on P2
(2)
Properly set the parameters corresponding to the regulators after setting parameter P2
(3)
The formula for the calculation of the CPT temperature is:
CPT temperature = {[(P7) x (temperature detected by the inlet air probe)] + [(100 - P7) x (temperature detected by the outlet air probe)] : 100}
(4)
the unit of measurement depends on P9 and P10
(5)
the value depends on parameter P2 (0,1 °C or 1 °F)
(6)
if parameter r12 is set to 0, the compressor will be switched on when the room temperature or CPT temperature is above the "working set-point + r0" and will be switched off when the
temperature falls below the working set-point; if parameter r12 is set to 1, the compressor will be switched on when the room temperature or CPT temperature is above the “working set-point
+ r0/2” and will be switched off when the temperature falls below the "working set-point - r0/2”