EVCO EVB1256N9D User Manual
Page 47

EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 47 of 92
C8
0
15
min
1
1
1
1
1
1
1
1
blocked compressor alarm delay (code “CSd”) (12)
C10
0
999
hx10
0
0
0
0
0
0
0
0
number of operating hours is higher than the limit at
which the need for maintenance is signalled
0
=
function absent
C11
0
240
s
3
3
3
3
3
3
3
3
minimum time interval between the switching on of two
different compressors (only if u1 and/or u11 = 7)
C12
0
10
- - - -
2
2
2
2
2
2
2
2
incidence of the number of compressor operation hours
on the choice of compressor to be switched on/off when
attempting to balance the number of operation hours and
the number of switch-ons of the two compressors ; see
also C13 (only if u1 and/or u11 = 7)
C13
0
10
- - - -
1
1
1
1
1
1
1
1
incidence of the switch-ons of the compressor on the
choice of compressor to be switched on/off when
attempting to balance the number of operation hours and
the number of switch-ons of the two compressors ; see
also C12 (only if u1 and/or u11 = 7)