C8

0

15

min

1

1

1

1

1

1

1

1

blocked compressor alarm delay (code “CSd”) (12)

C10

0

999

hx10

0

0

0

0

0

0

0

0

number of operating hours is higher than the limit at

which the need for maintenance is signalled

0

=

function absent

C11

0

240

s

3

3

3

3

3

3

3

3

minimum time interval between the switching on of two

different compressors (only if u1 and/or u11 = 7)

C12

0

10

- - - -

2

2

2

2

2

2

2

2

incidence of the number of compressor operation hours

on the choice of compressor to be switched on/off when

attempting to balance the number of operation hours and

the number of switch-ons of the two compressors ; see

also C13 (only if u1 and/or u11 = 7)

C13

0

10

- - - -

1

1

1

1

1

1

1

1

incidence of the switch-ons of the compressor on the

choice of compressor to be switched on/off when

attempting to balance the number of operation hours and

the number of switch-ons of the two compressors ; see

also C12 (only if u1 and/or u11 = 7)