EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 68 of 92
u2
0
1
- - - -
0
0
0
0
0
0
0
0
activation of room light switch on/off (in models EVB1204
and EVB1214 only if u1 = 0) or of the auxiliary output (in
models EVB1204 and EVB1214 only if u1 = 2, in the
remaining models only if u1 and/or u11 = 2) in manual
mode with the device turned off (40).
1
=
YES
u3
0
240
s
10
10
10
10
10
10
10
10
if C14 = 0 compressor switch-off delay after pump down
valve switch-off
if C14 = 1 or 2, maximum delay between pump down
valve switch-off and compressor switch-off
u4
0
1
- - - -
1
1
1
1
1
1
1
1
enabling of alarm output deactivation with the silencing of
the buzzer (in models EVB1204 and EVB1214 only if u1 =
3, in the remaining models only if u1 and/or u11 = 3)
1
=
YES
u5
-99.0
99.0
°C/°F
(1)
-1.0
-1.0
-1.0
-1.0
-1.0
-1.0
-1.0
-1.0
room temperature or CPT temperature below which the
door heating elements are turned on ("u5 - 2.0°C/4°F in
models
EVB1204
and
EVB1214
only
if
u1 = 4, in the remaining models only if u1 and u11 = 4).
u6
1
120
min
5
5
5
5
5
5
5
5
duration of demister heating elements activation (in
models EVB1204 and EVB1214 only if u1 = 1, in the
remaining models only if u1 and/or u11 = 1)
u7
-99.0
99.0
°C/°F
(1)
-5.0
-5.0
-5.0
-5.0
-5.0
-5.0
-5.0
-5.0
neutral area value (relative to the work set-point, i.e.
“work set-point + u7) (in models EVB1204 and EVB1214
only if u1 = 5, in the remaining models only if u1 and/or
u11 = 5) (41)